Abstract
In this paper, 72.5 kV oil-immersed bushing was produced in laboratory. The frequency-domain dielectric response tests of oil-immersed bushings were carried out at different test temperatures. The experimental data were fitted by using the modified double relaxation Cole-Cole dielectric model. The influence of temperature variation on the dielectric response test of the oil-immersed bushing and the Cole-Cole dielectric model parameters were analysed. The results showed that with the increase of the test temperature, the spectrum of the real and imaginary of the complex permittivity are shifted to the high frequency direction; the parameters of the dielectric model are significantly affected by temperature.
Export citation and abstract BibTeX RIS
Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.