Thermal Performance of a Cross-flow Rotating Spray Bed

, and

Published under licence by IOP Publishing Ltd
, , Citation Moumita Sharma et al 2020 IOP Conf. Ser.: Mater. Sci. Eng. 894 012013 DOI 10.1088/1757-899X/894/1/012013

1757-899X/894/1/012013

Abstract

This work examined the thermal performance of evaporative cooling of water by an air stream in an equipment wherein the liquid phase is sprayed between two coaxial disks. The contact between the two phases was in a cross-current mode. The performance of the spray bed in terms of thermal efficiency and evaporation rate of liquid were calculated by varying operational parameters like air flow rate, water flow rate, and rotational speed. Both the thermal efficiency (minimum = 0.183, maximum = 0.34) and evaporation rate (minimum = 0.009 kg/min, maximum = 0.032 kg/min) increased with rotational speed and air flow rate. However, the thermal efficiency decreased with liquid flow rate.

Export citation and abstract BibTeX RIS