Paper The following article is Open access

An improved design of damped AC test system for partial discharge measurement in distribution power cables

, , , , and

Published under licence by IOP Publishing Ltd
, , Citation Weisheng He et al 2018 IOP Conf. Ser.: Mater. Sci. Eng. 366 012029 DOI 10.1088/1757-899X/366/1/012029

1757-899X/366/1/012029

Abstract

This paper presents an improved technique to generate damped AC voltage for on-site PD detection on distribution power cables. The proposed technique is based on conventional frequency-tuned series resonant system and two additional high-speed switches. In order to reduce the size and weight of the proposed damped AC test system, electric simulation by Simulink and heat simulation by ANSYS are carried out to determine the system parameters. High-voltage test on two 10kV XLPE cable segments was conducted to validate the proposed technique.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.

Please wait… references are loading.
10.1088/1757-899X/366/1/012029