Abstract
The analysis on fault characteristic of Distribution Electronic Power Transformer (D-EPT) can help design its operation and protection scheme, hence improve the reliability of the D-EPT as well as the distribution power grid. The DC pole-to-pole short-circuit fault at DC-Link is analyzed with R-L-C resonant mode and free-wheeling mode, and the theoretical analysis on the short-circuit voltage and current is based on several influence factors and relevant system parameters, which indicates that the fault characteristics are related to the configuration, operation and system parameters of D-EPT.