This site uses cookies. By continuing to use this site you agree to our use of cookies. To find out more, see our Privacy and Cookies policy.
Paper The following article is Open access

Research on Real-Time Calculation Method of Transformer Temperature Field Based on Reduced Order Model and Sparse Measurement

, , , and

Published under licence by IOP Publishing Ltd
, , Citation Tao Wu et al 2024 J. Phys.: Conf. Ser. 2704 012030 DOI 10.1088/1742-6596/2704/1/012030

1742-6596/2704/1/012030

Abstract

The lifespan of transformers is closely related to their operating temperature. Among the existing temperature acquisition methods, the measurement method cannot obtain the complete temperature field temperature, while the numerical calculation method presents the challenge of significant computational expenses. This study theoretically derived how to determine the real-time temperature distribution of transformer windings based on sparse measurement data and reduced order models and solved sensor layout issues, including the number and placement position of sensors. In this study, the maximum calculation error of the temperature distribution is 1.8 K, and the calculation time is 0.38 seconds. The research findings suggest that multiple modes can contribute to the temperature distribution of a transformer. Under a constant load condition, the calculation of transformer temperature can be achieved by utilizing a temperature sensor positioned at the hot spot in conjunction with the first mode.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.

Please wait… references are loading.
10.1088/1742-6596/2704/1/012030