This site uses cookies. By continuing to use this site you agree to our use of cookies. To find out more, see our Privacy and Cookies policy.
Paper The following article is Open access

Modeling of a transient low-temperature waste heat recovery in the plate heat exchanger in Flownex Simulation Environment

, and

Published under licence by IOP Publishing Ltd
, , Citation K Zolińska et al 2022 J. Phys.: Conf. Ser. 2412 012004 DOI 10.1088/1742-6596/2412/1/012004

1742-6596/2412/1/012004

Abstract

The paper analyses the feasibility of determining the parameters of a heat exchanger operating in the crop production and realising low-temperature heat recovery from biological processes. For the first time, the Flownex 8.7 Simulation Environment has been used for this purpose. The temperature of the waste water was between 20 and 30°C. On the basis of the simulations, the power of the heat exchanger is determined to be 1 MW. The heat exchanger can efficiently heat up cold water from a deep well (7-10°C) to an assumed temperature of 19.7°C. The results from the simulation calculations correspond to the results obtained under actual conditions within a range of up to 2%.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.

Please wait… references are loading.
10.1088/1742-6596/2412/1/012004