Dynamic Capacitance Measurement of SF6 Circuit Breaker During Opening Operation

, , , , , and

Published under licence by IOP Publishing Ltd
, , Citation Jian Qin et al 2022 J. Phys.: Conf. Ser. 2310 012057 DOI 10.1088/1742-6596/2310/1/012057

1742-6596/2310/1/012057

Abstract

In order to mine the state information of SF6 circuit breakers (CBs) interruption chamber and evaluate the contacts state, a method of measuring and calculating the dynamic capacitance between contacts in CBs opening process was proposed. The test CB is connected in series with a high frequency AC power supply, and the voltage and current of the circuit breaker are measured during the opening process. The fundamental frequency components of the voltage and current are extracted by the short-time Fourier transform, and the dynamic capacitance curve as a function of time is calculated. The results show that due to the variation of capacitance, there are a large number of harmonics with frequencies close to the fundamental frequency in terminal voltage and current. During the first two cycles after contacts separation, the capacitance drops sharply to 33.25 pF, then with the increase of the contact distance, the capacitance decreases much more slowly and tends to be constant, and the capacitance is 20.70pF after the completion of the opening.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.

Please wait… references are loading.