Power grid practice of suppressing transient overvoltage of sending-end system by ultra high voltage direct current control parameters

, , , and

Published under licence by IOP Publishing Ltd
, , Citation Mingkai Yang et al 2022 J. Phys.: Conf. Ser. 2310 012036 DOI 10.1088/1742-6596/2310/1/012036

1742-6596/2310/1/012036

Abstract

The transient overvoltage off-grid problem of new energy in the sending-end network has become an important factor limiting the ultra high voltage direct current (UHVDC) transmission capacity. In this paper, the causes of transient overvoltage during the DC fault process is analysed firstly, then from the perspective of adjusting the reactive power consumption of the converter, taking the Qingyu UHVDC project in China as an actual simulation example, the influence of the DC control mode and current control parameters at the rectifier side on the transient overvoltage is deeply studied. Combined with the transient voltage evaluation results of the actual power grid, guiding suggestions for DC control strategies are given to improve the transmission capacity. The research results have important reference significance for improving the consumption of new energy and the transmission capacity of UHVDC projects.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.