Abstract

Through a macroscopic inspection, a stereomicroscopic inspection, a material analysis, a hardness inspection, a metallographic analysis, scanning electron microscope and energy spectrum analysis, the reasons for the breakage of the connecting bolts of the circuit breaker in a 500kV converter station are studied. The results show that the bolt fracture is caused by the combined effect of a hydrogen embrittlement and a high-stress low-cycle fatigue. The corresponding recommended measures are proposed to improve the reliability of the bolts and ensure the safe operation of the circuit breaker.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.