Abstract
Taking a 500kV dry type single circuit angle tower as the research object, the computational modal analysis of the established finite element calculation model is carried out. It is found that local vibration occurs at the bottom of the transmission tower. The weakness of the original structure lies in the intersection of the longest web, the deformation displacement of the joint is the largest, so the structure needs to be strengthened. There are two corresponding strengthening methods: Diamond reinforcement and positive cross reinforcement. Further analysis results show that the regular cross structure has a certain strengthening effect on the original structure.
Export citation and abstract BibTeX RIS