Paper The following article is Open access

Experiments and simulation analysis of 500kV single-phase three-column transformer in No-load under DC bias

, , , and

Published under licence by IOP Publishing Ltd
, , Citation Z Junshuang et al 2020 J. Phys.: Conf. Ser. 1585 012014 DOI 10.1088/1742-6596/1585/1/012014

1742-6596/1585/1/012014

Abstract

The DC-bias experiments were carried out on two identical single-phase autotransformers which parameters are 250MVA/500kV. The aim of the experiments was to test the ability of transformers for withstanding DC bias. The variation laws of the electrical quantity, the temperature rise, vibration with the increasing DC current under no-load are obtained. The effective value of the exciting current under DC bias is much higher than the normal no-load exciting current. The reference for the DC bias experiments of large transformers can be provided through this method.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.