Study on Fault Mechanism of Lightning Flashover Based on EMTP - RV in Wind Farm

, , , , , , and

Published under licence by IOP Publishing Ltd
, , Citation Shi Zhang et al 2019 J. Phys.: Conf. Ser. 1176 062020 DOI 10.1088/1742-6596/1176/6/062020

1742-6596/1176/6/062020

Abstract

The particularity of lightning flashover failure of wind farm is analyzed, and it is pointed out that the formation mechanism of lightning overvoltage in wind farm collector system is different from that of power system distribution network. On this basis, the mechanism of lightning flashover failure of wind farm collector system is analyzed. The EMTP-RV software is used to simulate the typical lightning over-voltage formation and propagation process of the wind farm collector system. Results show that the fault mechanism of the lightning flashover fault system is analyzed. Finally, it is pointed out that the design scheme of the insulation system of the wind farm collection system should not directly copy the design scheme of the distribution network of the power system.