Abstract
It is important in the petrochemical industry that there are high sensitivity, high accuracy, low-power consumption and intrinsically safe methods for the detection of propane, butane and their gas mixtures, to provide early warning of potential explosion hazards during both storage and transportation of oil and gas. This paper proposes a 'proof of principle' method for the detection of propane and butane using a Tunable Diode Laser Absorption Spectroscopy (TDLAS) technique over the near-infrared wavelength range from 1678nm to 1686nm. This method is relatively inexpensive to implement and is thus more practical, compared with detection methods using wavelengths further into the infra-red, near 3.3μm. The minimum detectable concentration was found to be low as 300ppm for propane or butane. Importantly, the relative measurement errors were all below 3% LEL, which meets the requirements from the petrochemical and oil-gas storage and transportation industries for a field-based system for monitoring of combustible gases.
Export citation and abstract BibTeX RIS
Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.