Analysing the influence of geometry and pressure on corona discharges

, and

Published 30 June 2022 © 2022 European Physical Society
, , Citation Jordi-Roger Riba et al 2022 Eur. J. Phys. 43 055201 DOI 10.1088/1361-6404/ac78a4

0143-0807/43/5/055201

Abstract

In this work, the authors propose an experiment aimed for undergraduate laboratories with the aim of introducing different novelties as a topic for practical sessions or student projects. The topics here investigated are appropriate for students with intermediate physics knowledge. Corona discharges are little studied in regular physics courses despite their practical importance in different areas, such as the distribution and transmission of electrical power, generation of ozone, particulate removal in air conditioning systems, improvement of wettability in polymeric materials, or the removal of electrostatic charges from the surface of airplanes among others. This work analyses the minimum voltage level leading to corona discharges and the influence of geometry and atmospheric pressure because these two factors are the most influential to determine the minimum voltage at which corona discharges appear.

Export citation and abstract BibTeX RIS

1. Introduction

To maximize efficiency and reduce operational costs, power transmission lines operate at very high-voltage levels. However, raising the voltage significantly increase the risk of electrical discharges, and in particular of corona activity, which have harmful effects on transmission lines. However, corona discharges are deliberately produced in various industrial processes such as the production of ozone in water treatment plants, the removal of particles in air conditioning systems or the improvement of the surface of polymeric materials. Corona activity can be controlled by adjusting the electric field strength on the surface of the high-voltage electrodes [1], because electrical discharges are triggered by the electric field strength.

In uniform electric fields as those generated between two parallel plates separated by atmospheric air, when the voltage between the two plates (electrodes) increases steadily, it will inevitably lead to a complete breakdown of the air gap. However, in the case of non-uniform electric fields, a gradual voltage increase first leads to partial discharges [2] and if the voltage is further increased, finally a complete breakdown of the gap will be produced. Corona is a type of partial discharge occurring in air (or a gas medium), i.e., a self-sustained luminous discharge that produces a conductive area around the electrode but it does not completely bridge the air gap between the two electrodes. When the maximum electric field intensity at the surface of conductor exceeds a certain value [3,4], corona initiates in a limited region surrounding the high-voltage electrode because air molecules become ionized [5] due to the impact of free electrons, hence developing an electron avalanche process [6]. Two regions can be distinguished within the air gap between the two metallic electrodes, i.e., the ionization and the low-field regions. The first one, with a usual size of several millimetres, is the area closest to the high-voltage electrode, having an intense electric field that sustains the ionization process. The low-field or drift region fills the inter-electrode space, so it comprises the region between the limit of the ionization area and the collecting electrode. The electric field in the low-field region cannot sustain the ionization process [7], so it stabilizes corona activity [8].

Positive and negative coronas reveal different voltage–current patterns, which is essentially due to the mass difference between electrons and positive ions [9]. However, a physical description of the phenomenon is complex due to the ionization process and the chemical reactions occurring within the gas during the discharge process [10]. In power systems, corona discharges must be avoided, because they produce negative effects, and reduce their performance due to the power losses and generation of chemical by-products, such as ozone and nitrogen oxides among others [11]. The corona activity produces acoustic and electromagnetic emissions, including ultraviolet and visible light, and radio interference noise. Since most of the radiation produced by corona activity falls within the UV spectrum, it is almost invisible in daylight. Due of the complexity of the phenomenon, there are no theoretical formulas to determine the critical electric field at which corona initiates, so that for a given geometry, the conditions leading to corona are usually determined from experimental data.

Several variables influence the onset of corona, such as the type of voltage applied (direct current or alternating current, low or high frequency), geometry, surface state, or weather conditions (air temperature, pressure, density, pressure, humidity or pollution). Apart of the applied voltage level, geometry and atmospheric pressure play a leading role.

It is well known that the electric field near a sharp edge of a conductor is higher, so the electric field lines are more closely spaced nearer the conductor compared to a flat conductor. Therefore, electrical discharges are more likely to occur in areas of the electrode surface with smaller radius.

The dielectric strength of air is greatly reduced with pressure [1214], so at high altitude (lower pressure), lower voltages are required to initiate corona discharges compared to sea level. Electrical installations in the Andes or the Himalayas, where altitudes between 4500 and 5300 m are possible and need special attention, because at 5000 m the pressure is reduced by about 45% compared to that at sea level. Similar or even stronger effects occur in electrical installations found in aircrafts, because most commercial jetliners have a service ceiling of about 42 000 ft (12.8 km), so electronic and electrical systems found in unpressured compartments must withstand pressures in the 17–101 kPa range.

Because of the multiphysics origin and the complexity of corona discharges, there are no theoretical-based analytical formulas to describe the conditions at which corona discharges initiate. This paper presents a method for determining the effect of geometry and atmospheric pressure on the minimum voltage at which corona discharges can develop. Although spherical electrodes are discussed, the method applied here can be generalized to other types of electrodes. The approach proposed in this paper can be applied to develop a project or a laboratory practical for undergraduate courses. Regardless of the importance and practical impact of corona discharges on electrical systems, this topic is infrequently studied in regular courses, so to overcome this problem, this work proposes a students' project or practical session to analyse this subject from an experimental point of view.

This paper is organized as follows. Section 2 explains two of the most influential factors affecting corona discharges, i.e., geometry and air pressure. Section 3 develops the experimental procedure to find the corona extinction voltage (CEV). Section 4 details the analysed electrodes and the experimental setup used in the experiments. Section 5 presents and discusses the experimental results. Finally, section 6 summarizes the conclusions of this work.

2. Factors influencing corona discharges

This section briefly discusses two of the most influential factors affecting corona discharges, i.e., geometry and atmospheric pressure.

2.1. Effect of geometry on corona discharges

As explained, geometry and specifically the curvature radius play a key role to determine the minimum voltage level at which corona activity can be detected, which is known as the CEV.

This paper studies spherical electrodes to analyse the effect of the geometry on the CEV value, as they are low-cost (steel bearing balls are used), have a definite and regular radius and a uniform surface finish. As the electric field near a sharp conductor is known to be higher, it is expected that when dealing with small radius spheres, corona activity will start at lower CEV values compared to those expected in larger spheres.

Figure 1 shows the electric field distribution generated by two sphere-plane electrodes with different sphere radii under the same conditions (applied voltage and sphere-plane separation).

Figure 1.

Figure 1. (a) Electric field lines on the surface of a spherical electrode of radius 1 mm placed 80 mm above a ground plane. (b) Electric field lines on the surface of a spherical electrode of radius 5 mm placed 80 mm above a ground plane.

Standard image High-resolution image

Figure 1 shows that the electric field strength at the surface points of the largest sphere is lower than that of the smaller spherical electrode. It can be seen by the lower density of electric field lines on its surface.

2.2. Effect of pressure on corona discharges

Table 1 shows the standardized relationships among air temperature, pressure and density according to the US standard atmosphere [15].

Table 1. Relationships among altitude, pressure and air density according to the US standard atmosphere [15].

Altitude (m)Temperature (°C)Pressure (kPa)Air density (kg m−3)Relative air density (−)
015.0101.3251.2251.000
10008.589.8751.1120.907
20002.079.4951.0060.822
3000−4.570.1090.9090.742
4000−11.061.6400.8190.669
5000−17.554.0200.7360.601
6000−14.047.1810.6600.539
7000−30.541.0610.5900.481
8000−37.035.6000.5250.429
9000−43.530.7420.4660.381
10 000−50.026.4360.4120.337
11 000−56.522.6320.3640.297
12 000−56.519.3300.3110.254

Pressure has a deep influence on the minimum voltage level at which corona discharges initiate, so in view of the values in table 1, this paper will consider the pressure range between 100 kPa and 20 kPa to cover the 0–12 000 m altitude range. It is well known that the minimum voltage level at which corona discharges initiate decline with atmospheric pressure, i.e., at increasing altitudes. This is due to the fact that the mean free path of electrons increases when the air pressure decreases, so there are fewer collisions in the path of the electrons between the electrodes, but they are more energetic that at higher pressures, thus making the ionization process more effective [16].

2.3. Peek's law for visual corona

Peek's law [17] was derived more than a century ago using experimental data obtained from cylindrical conductors and it is widely accepted. It states that the visual electric field strength Ec at the surface of the conductor when visual corona effect starts can be expressed as,

Equation (1)

where E0 (kVpeak/cm) is the visual critical electric field strength measured at standard atmospheric conditions, a (cm1/2) is an empirical constant, R (cm) is the radius of the conductor, m is the roughness factor, and δ [-] is the relative air density, whose value depends on the atmospheric pressure. According to peek, E0 = 29.8 kVpeak/cm and a = 0.301 cm1/2, under 50 Hz alternating current supply.

It is worth noting that the relative air density δ can be expressed as the ratio between the local and standard atmospheric pressures δk = PxkPa/P100kPa, thus the pressure ratio k plays a key role in the strength of the visual critical electric field Ec.

In this experiment, the sizes of the spheres are small compared to the distance to the ground plate, so the equipotential curves adjacent to the sphere electrodes are nearly spherical in shape. Since the electric potential and field are related by V = −∫Edr, by integrating (1) in the surroundings of the boundary of the sphere and assuming m = 1 (we use perfectly polished bearing balls), it results the following expression of the corona visual voltage Vc,

Equation (2)

It is noted that (2) is not a conventional equation found in technical books, but an hypothesis that needs to be verified from experimental data. Rewriting (2), it leads to (3),

Equation (3)

According to (3), a linear fit of Vc/kR as function of 1/(kR)1/2 should yield the values for E0 and a.

2.4. Paschen's law

It is well known that air density and atmospheric pressure have a strong influence on the dielectric properties of gases [18], and in particular on the voltages at which corona and complete breakdown occur. Paschen [19] carried out studies of gaseous spark gap breakdown in uniform fields generated between two parallel plate electrodes in different gases, including air at different pressures. Figure 2 shows the Paschen's curve for air at 20 °C based on the work of Dakin et al [20].

Figure 2.

Figure 2. Experimental Paschen curve for air at 20 °C adapted from [20, 21], where d is the spacing between the electrodes and p is the pressure of air.

Standard image High-resolution image

According to the Paschen's curve for air shown in figure 2, the breakdown voltage in uniform fields decreases when the pd product reduces, where p is the pressure of air and d is the distance between the parallel plate electrodes. However, for very low pressure levels (relative vacuum conditions), the breakdown voltage increases when the pd product reduces. Therefore, Paschen's law states that the pdproduct of the pressure and a characteristic distance, in our experiment the kR product, determines the breakdown voltage. So the kR product is already present in Peek's law as observed in (1)–(3) and throughout the field of discharge physics.

3. Procedure to determine the CEV value

As detailed in the IEC 60270 standard [22], when gradually increasing the voltage from zero, the first point at which corona activity appears is known as corona inception voltage. However, when initiated, if the voltage is reduced, corona activity still can be observed until reaching a minimum voltage value known as CEV, which is the lowest value of the voltage at which corona activity can be registered.

Figure 3 shows the procedure applied to detect the CEV value under 50 Hz alternating current supply.

Figure 3.

Figure 3. Applied experimental method for determining the CEV value of the analysed sphere-to-plane air gaps.

Standard image High-resolution image

4. Analysed electrodes and experimental setup

This section describes the samples analysed and the experimental setup.

4.1. Analysed spherical electrodes

The analysed sphere-to-plane gaps include a grounded square copper plate and stainless steel bearing balls of different diameters in the 2–10 mm range. They are mechanically and electrically connected to stainless steel tubes whose diameters are compressed in the 0.75–1.92 mm range, as shown in figure 4. The diameter of the tubes was carefully selected and matched with that of the spheres to minimize their influence. The lowest part of the sphere electrodes was placed 80 mm above the ground plane. Temperature was kept constant at 25 °C during the experiments.

Figure 4.

Figure 4. Analysed spherical electrodes.

Standard image High-resolution image

4.2. Experimental setup

Corona tests performed in this work require a high voltage source. A low-voltage variable-amplitude ac source (APM Technologies SP300VAC600W, 0–300 V) was used to this end connected to a step-up high-voltage transformer (turns ratio 1:100, 36 kV maximum voltage, Laboratorio Electrotécnico). To measure the output voltage of the high-voltage transformer, a high-voltage probe (Testec TT-HVP40, voltage divider 1.000:1) was connected to a true-RMS voltmeter (Fluke 289).

Low-pressure experiments were performed in a low-pressure cylindrical chamber (diameter = 130 mm diameter and height = 375 mm) that incorporates a sealed lid and a hermetic pass through connector that allows passing thin wires from the inside to the outside of the low-pressure camera. The pressure was regulated using a vacuum pump (Bacoeng BA-1).

A gas-filled tube UV sensor (R9533-UVTRON, Hamamatsu) was used inside the low-pressure chamber to detect the corona discharges. This sensor is sensitive to the 185–265 nm range and uses the photoelectric effect of a metallic electrode and the gas multiplication of the electric current due to the electric discharge.

Figure 5 shows a layout of the experimental setup.

Figure 5.

Figure 5. Sketch of the experimental arrangement used in this work to detect the corona discharges at varying pressure conditions.

Standard image High-resolution image

5. Results

This section presents and discusses the experimental values obtained in the laboratory. It is worth noting that further information and a more extensive data set can be found in a previous research paper of the authors [2].

First, to better understand how corona discharges look like, figure 6 shows long exposure photographs of such discharges taken with a high-resolution CMOS imaging sensor (Sony IMX586). In a previous work [23] the authors have shown that the energy contained in such photographs is proportional to the electric power dissipated by the discharges.

Figure 6.

Figure 6. Long exposure photographs of the corona discharges. (a) Corona photograph of the spherical electrodes used at 100 kPa, 28 kV. (b) Corona photograph of the spherical electrodes used at 60 kPa, 20 kV. (c) Corona photograph of the spherical electrodes used at 20 kPa, 8 kV.

Standard image High-resolution image

5.1. Measured CEV values

Experimental results are presented in table 2. CEV values were measured according to the procedure described in figure 3 using the experimental setup shown in figure 5.

Table 2. Summary of experimental values of the measured CEV values under 50 Hz alternating current supply.

Air pressure (kPa)Sphere diameter (mm)CEV (Corona extinction voltage) (kVpeak)
20 23.099
33.901
44.542
55.055
65.522
 76.371
 86.829
 97.154
 107.600
40 24.967
36.280
47.307
58.508
69.071
 710.519
 811.312
 912.117
 1013.381
60 26.574
38.285
49.596
 511.241
 612.516
 713.961
 815.134
 916.180
 1017.232
80 27.962
310.129
411.748
513.843
615.495
 717.001
 818.288
 919.665
 1021.487
100 29.576
311.972
414.880
516.731
618.717
 719.913
 821.630
 923.467
 1025.731

5.2. Validation of the Peek's law from experimental data

This subsection confirms the validity of Peek's law. The experimental values presented in table 2 are arranged properly in figure 7, which plots Vc/(kR) versus (kR)−1/2 and the experimental fit according to (3), where Vc is the experimental CEV value. From this linear fit it results E0 = 26.99 kVpeak/cm and a = 0.336 cm−1/2 with a coefficient of determination R2 = 0.9606. Note that the obtained values of E0 and a are very close to the ones reported by Peek when analysing parallel cylindrical conductors, thus corroborating the applicability of Peek's equation.

Figure 7.

Figure 7. (a) Experimental values from table 2 plotted as Vc/(kR) versus (kR)−1/2 and the experimental fit according to equation (3), where Vc is the experimental CEV value. From the linear fit it results E0 = 26.99 kVpeak/cm and a = 0.336 cm−1/2. (b) Experimental values of Vc versus kR and results of equation (2) versus kR using E0 = 26.99 kVpeak/cm and a = 0.336 cm−1/2.

Standard image High-resolution image

Results presented in figure 7(b) show that all values in table 2 (it considers different pressures) collapse onto a single curve, thus confirming Paschen's law and the correct shape of equation (2).

5.3. Influence of the radius and pressure on the CEV values

Figure 8 shows a graphical visualization of the experimental CEV values presented in table 2 as a function of the sphere diameter and atmospheric pressure.

Figure 8.

Figure 8. Summary of the experimental CEV values obtained in the 20–100 kPa range using spherical electrodes in the 2–10 mm diameter range.

Standard image High-resolution image

Results presented in figure 8 clearly show the key role of the diameter and pressure on the CEV values. Whereas the CEV value considerably increases with the diameter of the spherical electrode, it reduces with pressure.

Figures 9 and 10 show these effects with more detail to better understand their role on the CEV value.

Figure 9.

Figure 9. Pressure effect. (a) Ratio between the CEV values measured at 80–60–40–20 kPa and the CEV values measured at 100 kPa for the different spherical electrodes. (b) Average values of the CEVxkPa/CEV100kPa as a function of pressure and its linear fit that results in a coefficient of determination R2 = 0.9973.

Standard image High-resolution image
Figure 10.

Figure 10. Geometry effect. (a) Ratio of the CEV values for 2–to–9 sphere diameters to the CEV values for 10 mm sphere diameter at different pressures. (b) Average values of the CEVxmma/CEV10mm as a function of the sphere diameter and its linear fit that results in a coefficient of determination R2 = 0.9954.

Standard image High-resolution image

Figure 9 shows the ratio between the CEV values measured at 80–60–40–20 kPa and the CEV values measured at 100 kPa, CEVxkPa/CEV100kPa for the different spherical electrodes.

Results presented in figure 9 clearly show the important effect of the atmospheric pressure on the CEV value. As expected, for a given pressure, the CEVxkPa/CEV100kPa ratio is almost independent of the radius of the spherical electrode and it decreases linearly with the reduction of pressure.

Figure 10 shows the effect of the electrode diameter for each pressure. It shows the ratio of the CEV values for 2–to–9 sphere diameters to the CEV values for the 10 mm sphere diameter at different pressures, CEVxmm/CEV10mm. As expected, when the diameter of the spherical electrode reduces, this ratio also reduces because CEV values decrease with the diameter of the electrode. Results in figure 10 also show that for a given pressure, the CEVxmm/CEV10mm ratio is almost independent of the pressure. These results show the important role that the diameter plays on the CEV value.

Results presented in figure 10 clearly show that the CEVxmm/CEV10mm ratio is almost independent of the atmospheric pressure and decreases linearly with the reduction of the sphere radius.

6. Conclusion

In this work, the authors have proposed an experiment for undergraduate laboratories. It has introduced topics related to electrical discharges, that are suitable for students with intermediate physics knowledge. The experiments proposed in this paper can be applied for student projects or in practical sessions. Corona discharges are scarcely studied in regular physics courses despite their practical importance in different areas. This work has analysed the effect of geometry and atmospheric pressure on the CEV of spherical electrodes. The results presented clearly show that as the pressure and the diameter of the electrode decrease, CEV values also decrease.

We consider that the topics studied in this paper are worth for a students' project or a practical session for undergraduate laboratories, because they involve basic knowledge of electricity and fluids. The practical work could be oriented to study the combined effect of pressure and geometry on the minimum voltage at which corona discharges initiate, to analyse both effects separately or even to only study the effect of geometry.