Research on Selection Method for AVC Control Command of Continuous Variable Equipment

, , , , , , and

Published under licence by IOP Publishing Ltd
, , Citation Shangfeng Xiong et al 2019 IOP Conf. Ser.: Earth Environ. Sci. 223 012019 DOI 10.1088/1755-1315/223/1/012019

1755-1315/223/1/012019

Abstract

The existing AVC system uses the expected voltage value as the control command value of the continuous adjustable reactive power source. However, the phenomenon of "grabbing reactive power", which is caused by the difference in the adjustment speeds of various continuous adjustable reactive power sources, is not conductive to safe, economical and high-quality operation of the power grid. To solve this problem, a method of selecting AVC control command is proposed, in which the expected voltage value as control command is delivered to the continuous adjustable voltage source with high sensitivity and fast adjustment speed and the expected reactive power is delivered to the rest. This method, combined with the existing AVC system, forms an AVC control command selection system to effectively solve the problem of "grabbing reactive power" and ensure safe, economical and high-quality operation of the power grid.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.

Please wait… references are loading.
10.1088/1755-1315/223/1/012019